Alvarez Arboleda, BayronVelasco Méndez, Jose RicardoMesa Monsalve, Yeison AlexanderQuintana Martinez, Josman JoseTaborda Vergara, Dumas Alejandro2026-05-202026-05-202025https://repositorio.pascualbravo.edu.co/handle/pascualbravo/3239La presente auditoría energética se realizó en la empresa SOMELECT SAS, especializada en distribución y fabricación de componentes eléctricos, con el objetivo de identificar oportunidades de mejora en el uso y gestión eficiente de la energía eléctrica. Mediante el empleo de tecnología IoT (sistema DRACMON-3) y metodología conforme a los estándares ISO 50001 e ISO 50002, se capturaron y analizaron datos de consumo eléctrico durante 24 días en horario operativo (8:00 AM - 7:00 PM). Los resultados revelaron que la maquinaria industrial concentra el 94.4% del consumo (2,250 kW), mientras que se identificaron ineficiencias críticas: un severo desequilibrio trifásico del 63.76% y un factor de potencia promedio de 0.890, por debajo del estándar recomendado de 0.95. El análisis permitió cuantificar seis oportunidades de mejora prioritarias, encabezadas por el balanceo de fases y la compensación de reactivos. La implementación integral del plan de acción propuesto proyecta una reducción del 20.4% en consumo energético (pasando de 1,368,930 a 1,089,544 kWh mensuales), generando ahorros de $256.5 millones COP mensuales ($1,676 mil millones anuales) con una inversión de $205-292 millones COP. El retorno de inversión extraordinario de apenas 1.4-1.8 meses, combinado con beneficios ambientales (reducción de 1,600 toneladas CO₂ anuales), posiciona a SOMELECT como referente en eficiencia energética industrial y cumplimiento de normativas nacionales e internacionales.Abstract This energy audit was conducted at SOMELECT SAS, a company specializing in the distribution and manufacturing of electrical components, to identify opportunities for improvement in efficient use and management of electrical energy. Using IoT technology (DRACMON-3 system) and methodology compliant with ISO 50001 and ISO 50002 standards, electrical consumption data were captured and analyzed over 24 days during operating hours (8:00 AM - 7:00 PM). The results revealed that industrial machinery concentrates 94.4% of consumption (2,250 kW), while critical inefficiencies were identified: severe three-phase imbalance of 63.76% and average power factor of 0.890, below the recommended standard of 0.95. The analysis quantified six priority improvement opportunities, led by phase balancing and reactive power compensation. The comprehensive implementation of the proposed action plan projects a 20.4% reduction in energy consumption (from 1,368,930 to 1,089,544 kWh monthly), generating savings of $256.5 million COP monthly ($1,676 billion annually) with an investment of $205-292 million COP. The extraordinary return on investment of only 1.4-1.8 months, combined with environmental benefits (reduction of 1,600 tonnes CO₂ annually), positions SOMELECT as a benchmark in industrial energy efficiency and compliance with national and international regulations.application/pdfspahttps://creativecommons.org/licenses/by-nc-nd/4.0/Auditoría energética para la optimización del consumo eléctrico en la empresa SOMELECT S.A.S. utilizando medición remotainfo:eu-repo/semantics/openAccesshttp://purl.org/coar/resource_type/c_7a1fUso racional de la energíaEficiencia energéticaAtribución-NoComercial-SinDerivadas 4.0 Internacional (CC BY-NC-ND 4.0)Desequilibrio trifásicoEnergy auditEnergy efficiencyAuditoría energéticaAhorro de energía eléctricaInternet de las cosasConsumo de energía